SIMATIC S7-1200, Digital output SM 1222, 8 DO, Relay Changeover contact
|
General information
|
Product type designation
|
SM 1222, DQ 8x relay/2 A
|
Supply voltage
|
permissible range, lower limit (DC)
|
20.4 V
|
permissible range, upper limit (DC)
|
28.8 V
|
Input current
|
from backplane bus 5 V DC, max.
|
140 mA
|
Digital outputs
|
● from load voltage L+, max.
|
16.7 mA/relay coil
|
Power loss
|
Power loss, typ.
|
5 W
|
Digital outputs
|
Number of digital outputs
|
8
|
● in groups of
|
1
|
Short-circuit protection
|
No; to be provided externally
|
Switching capacity of the outputs
|
● with resistive load, max.
|
2 A
|
● on lamp load, max.
|
30 W with DC, 200 W with AC
|
Output voltage
|
● Rated value (DC)
|
5 V DC to 30 V DC
|
● Rated value (AC)
|
5 V AC to 250 V AC
|
Output current
|
● for signal "1" rated value
|
2 A
|
Output delay with resistive load
|
● "0" to "1", max.
|
10 ms
|
● "1" to "0", max.
|
10 ms
|
Total current of the outputs (per group)
|
horizontal installation
|
— up to 50 °C, max.
|
2 A; Current per mass
|
Relay outputs
|
● Number of relay outputs
|
8
|
● Rated supply voltage of relay coil L+ (DC)
|
24 V
|
● Number of operating cycles, max.
|
mechanically 10 million, at rated load voltage 100 000
|
Switching capacity of contacts
|
— with inductive load, max.
|
2 A
|
— on lamp load, max.
|
30 W with DC, 200 W with AC
|
— with resistive load, max.
|
2 A
|
Cable length
|
● shielded, max.
|
500 m
|
● unshielded, max.
|
150 m
|
Interrupts/diagnostics/status information
|
Alarms
|
● Diagnostic alarm
|
Yes
|
Diagnostics indication LED
|
● for status of the outputs
|
Yes
|
Potential separation
|
Potential separation digital outputs
|
● between the channels
|
Relays
|
● between the channels, in groups of
|
1
|
● between the channels and backplane bus
|
1500 V AC for 1 minute
|
Permissible potential difference
|
between different circuits
|
750 V AC for 1 minute
|
Degree and class of protection
|
Degree of protection acc. to EN 60529
|
|
● IP20
|
Yes
|
Standards, approvals, certificates
|
CE mark
|
Yes
|
CSA approval
|
Yes
|
UL approval
|
Yes
|
cULus
|
Yes
|
FM approval
|
Yes
|
RCM (formerly C-TICK)
|
Yes
|
Marine approval
|
Yes
|
Ambient conditions
|
Free fall
|
● Fall height, max.
|
0.3 m; five times, in product package
|
Ambient temperature during operation
|
● min.
|
-20 °C
|
● max.
|
60 °C; Number of simultaneously activated outputs: 4 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 at 55 °C horizontal or 45 °C vertical
|
● horizontal installation, min.
|
-20 °C
|
● horizontal installation, max.
|
60 °C
|
● vertical installation, min.
|
-20 °C
|
● vertical installation, max.
|
50 °C
|
● permissible temperature change
|
5°C to 55°C, 3°C / minute
|
Ambient temperature during storage/transportation
|
● min.
|
-40 °C
|
● max.
|
70 °C
|
Air pressure acc. to IEC 60068-2-13
|
● Storage/transport, min.
|
660 hPa
|
● Storage/transport, max.
|
1 080 hPa
|
Relative humidity
|
● Operation at 25 ℃ without condensation, max.
|
95 %
|
Connection method
|
required front connector
|
Yes
|
Mechanics/material
|
Enclosure material (front)
|
|
● Plastic
|
Yes
|
Dimensions
|
Width
|
70 mm
|
Height
|
100 mm
|
Depth
|
75 mm
|
Weights
|
Weight, approx.
|
310 g
|